Home > Brand > Schneider

Schneider  NSX   Series  LV431748
  • Schneider  NSX   Series  LV431748
  • Schneider  NSX   Series  LV431748
  • Schneider  NSX   Series  LV431748
  • Schneider  NSX   Series  LV431748

Schneider NSX Series LV431748

Circuit breaker ComPact NSX250F, 36 kA at 415 VAC, MA trip unit 220 A, 3 poles 3d


Share
  • Description
  • Prameters
  • Equipment photos
Main
rangeComPact
product nameComPact NSX
range of productComPact NSX100...250
device short nameNSX250F
product or component typeCircuit breaker
device applicationMotor
Number of poles3P
protected poles description3t
[In] rated current220 A at 65 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
network typeAC
network frequency50/60 Hz
suitability for isolationYes conforming to EN/IEC 60947-2
utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity85 kA at 240 V AC 50/60 Hz conforming to UL 508
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 600 V AC 50/60 Hz conforming to UL 508

Performance levelF 36 kA 415 V AC
trip unit nameMA
trip unit technologyMagnetic
trip unit protection functionsI
control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2

mechanical durability20000 cycles
electrical durability5000 cycles at 690 V In
10000 cycles at 690 V In/2
10000 cycles at 440 V In
20000 cycles at 440 V In/2

mounting supportBackplate
upside connectionFront
downside connectionFront
connection pitch35 mm
protection typeI : for short-circuit protection (magnetic)
trip unit rating220 A at 65 °C
Short-time protection pick-up adjustment type IsdAdjustable
[Isd] Short-time protection pick-up adjustment range9...14 x In
earth-leakage protectionWithout
Number of slots for electrical auxiliaries5 slot(s)
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
net weight2.4 kg
Environment
standardsEN/IEC 60947
product certificationsCCC
Marine
EAC

overvoltage categoryClass II
electrical shock protection classClass II
pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
ambient air temperature for operation-25…70 °C
ambient air temperature for storage-50…85 °C
relative humidity0…95 %
operating altitude0...2000 m without derating
2000 m...5000 m with derating

Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Weight1.951 kg
Package 1 Height11.6 cm
Package 1 width14.4 cm
Package 1 Length19.3 cm
Unit Type of Package 2S04
Number of Units in Package 212
Package 2 Weight24.178 kg
Package 2 Height30 cm
Package 2 width40 cm
Package 2 Length60 cm
Offer Sustainability
Sustainable offer statusGreen Premium product
REACh RegulationREACh Declaration
EU RoHS DirectiveCompliant
EU RoHS Declaration

Mercury freeYes
RoHS exemption informationYes
China RoHS RegulationChina RoHS declaration
Product out of China RoHS scope. Substance declaration for your information

Environmental DisclosureProduct Environmental Profile
Circularity ProfileEnd of Life Information
WEEEThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins
Contractual warranty
Warranty18 months


Copyright © Changzhou Wheat Automation Technology Co., Ltd All Rights Reserved | Sitemap |Powered by