Circuit breaker ComPact NSX100B, 25 kA at 415 VAC, TMD trip unit 16 A, 3 poles 3d


Share
  • Description
  • Prameters
  • Equipment photos
Main
rangeComPact
product nameComPact NSX
range of productComPact NSX100...250
device short nameNSX100B
product or component typeCircuit breaker
device applicationDistribution
Number of poles3P
protected poles description3t
[In] rated current16 A at 40 °C
[Ue] rated operational voltage690 V AC 50/60 Hz
network typeAC
network frequency50/60 Hz
suitability for isolationYes conforming to EN/IEC 60947-2
utilisation categoryCategory A
[Icu] rated ultimate short-circuit breaking capacity15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2

Performance levelB 25 kA 415 V AC
trip unit nameTM-D
trip unit technologyThermal-magnetic
trip unit protection functionsLI
control typeToggle
Circuit breaker mounting modeFixed
Complementary
[Ui] rated insulation voltage800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Ics] rated service short-circuit breaking capacity20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
7.5 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2

mechanical durability50000 cycles
electrical durability10000 cycles at 690 V In
20000 cycles at 690 V In/2
30000 cycles at 440 V In
50000 cycles at 440 V In/2

mounting supportBackplate
upside connectionFront
downside connectionFront
connection pitch35 mm
protection typeL : for overload protection (thermal)
I : for short-circuit protection (magnetic)

trip unit rating16 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)Adjustable
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Long-time protection delay adjustment type trFixed
[tr] long-time protection delay adjustment range120…400 s at 1.5 x In
15 s at 6 x Ir

Short-time protection pick-up adjustment type IsdFixed
[Isd] Short-time protection pick-up adjustment range190 A
Short-time protection delay adjustment type tsdFixed
earth-leakage protectionWithout
Number of slots for electrical auxiliaries5 slot(s)
Width (W)105 mm
Height (H)161 mm
Depth (D)86 mm
net weight2.05 kg
Environment
standardsEN/IEC 60947
product certificationsCCC
EAC
Marine

overvoltage categoryClass II
electrical shock protection classClass II
pollution degree3 conforming to IEC 60664-1
IP degree of protectionIP40 conforming to IEC 60529
IK degree of protectionIK07 conforming to IEC 62262
ambient air temperature for operation-25…70 °C
ambient air temperature for storage-50…85 °C
relative humidity0…95 %
operating altitude0...2000 m without derating
2000 m...5000 m with derating

Packing Units
Package 1 Weight1.811 kg
Package 1 Height14.400 cm
Package 1 width11.600 cm
Package 1 Length19.400 cm
Offer Sustainability
Sustainable offer statusGreen Premium product
REACh RegulationREACh Declaration
EU RoHS DirectiveCompliant
EU RoHS Declaration

Mercury freeYes
RoHS exemption informationYes
China RoHS RegulationChina RoHS declaration
Product out of China RoHS scope. Substance declaration for your information

Environmental DisclosureProduct Environmental Profile
Circularity ProfileEnd of Life Information
Contractual warranty
Warranty18 months


Copyright © Changzhou Wheat Automation Technology Co., Ltd All Rights Reserved | Sitemap |Powered by